Victron
Victron Energy - Energy Meter - VM-3P75CT - 3 Phase - 75A
Victron Energy - Energy Meter - VM-3P75CT - 3 Phase - 75A
Couldn't load pickup availability
Victron VM-3P75CT Energy Meter: 3-Phase Monitoring with Split-Core CTs
Direct-to-GX Metering via VE.Can or Ethernet, No RS485 Interface Needed
The Victron VM-3P75CT is a three-phase (also usable as single- or split-phase) energy meter that measures power and energy and broadcasts it directly to a Victron GX device over VE.Can or Ethernet, with no separate RS485-to-USB interface needed to get started. It is rated at 75A per phase and can measure up to 80A RMS per phase, using three split-core current transformers supplied ready-wired with 640mm leads, so the meter can be fitted around existing conductors without breaking into the wiring.
Two RJ45 VE.Can ports (with terminators included) connect the meter directly to a GX device's VE.Can network for a simple, network-independent connection, while the built-in Ethernet port uses Modbus UDP to join an existing local network at a 100ms refresh rate. Both connection methods feed live data to the VRM Portal as well as the VictronConnect app, which also handles all configuration, including setting the meter's role, phase configuration and energy registration method.
Beyond basic grid, PV inverter, generator and AC load metering, the VM-3P75CT can also be assigned to track an EV charger or heat pump circuit, and it reports line-to-neutral and line-to-line voltage, power factor, phase sequence and phase rotation warnings for more detailed diagnostics than a basic kWh meter.
Key Features
- 75A rated per phase (measures up to 80A RMS), via three split-core CTs with 640mm leads - no need to break into existing wiring
- VE.Can or Ethernet connection to the GX device, with no RS485 interface cable required
- Configurable roles: grid meter, PV inverter, AC genset, AC load, EV charger or heat pump
- Single-, split- or three-phase operation from the one meter
- Reports voltage, power factor, phase sequence and phase rotation warnings in addition to power and energy
- IP20 polycarbonate enclosure, DIN-rail mounted, 90 x 71 x 59mm
Installation
The VM-3P75CT self-powers from its L1-N connection and requires an external switch or circuit breaker as a disconnecting device (not included). Voltage wiring connects via 1.0-2.5mm² screw terminals, and the pluggable current transformer terminals make swapping a damaged CT straightforward. The meter is rated for indoor use only, from -10°C to +55°C.
Specifications
| Victron Part Number | REL200300100 |
|---|---|
| Phases | 1, split-phase or 3 |
| Rated Current | 75A per phase (measures up to 80A RMS) |
| Current Connection | 3x split-core current transformers, 640mm leads (included) |
| Voltage Inputs | 85-265V L-N, 150-460V L-L |
| Communication | VE.Can (2x RJ45, terminators included) or Ethernet (Modbus UDP) |
| Refresh Rate | 100ms |
| Power Consumption | 1.45W / 3.1VA (self-powered via L1-N) |
| Protection Category | IP20 |
| Enclosure | Polycarbonate, blue (RAL5012), DIN-rail mount |
| Dimensions | 90 x 71 x 59mm |
| Weight | 370g (including packaging) |
| Operating Temperature | -10°C to +55°C, indoor only |
Share